Acrel Aim Series Industrial Insulation Monitoring Device Low Voltage AC/DC It System with Alarm Suitable for Mining Aim
Product DescriptionAIM-T300 Grounf Fault Detectors Insulation Monitoring Device for Ungrounded System GeneralAIM-T300 in
Description
Basic Info.
Model NO. | AIM-T300 |
Transport Package | Fob Shanghai |
Trademark | ACREL |
Origin | China |
Production Capacity | 10000PCS/Per Month |
Product Description
Product DescriptionAIM-T300 Grounf Fault Detectors Insulation Monitoring Device for Ungrounded SystemGeneralAIM-T300 insulation monitoring device is an instrument developed for monitoring the insulation status of IT distribution system (ungrounded system) to ground with many years of design experience in the power instrument industry.The products adopt advanced microcontroller technology, high integration, small size, easy to install, intelligent, digital, networking in one.Instrument has a unique barrier because early warning, fault alarm, event records, such as a variety of functions, can be used for mine, metallurgy, glass, electric furnace and test equipment factory, chemical plants, explosive dangerous location, computer center and emergency power supply and other places IT power distribution system, real-time monitoring IT power distribution system of insulation condition, when the insulation fault occurs, alarm in time, to remind staff some troubleshooting.
FeaturesAC, DC main circuitsAC/DC main circuits with directly connected DC components, such as rectifiersSystems with switch-mode power suppliesCommunication:RS485(Modbus-RTU)Display:128x64 bits LCD with real-time insulationresistance and leakage capacitance value displayApplicable system voltage range:Up to 450V (AC,DC,AC&DC)
Technical Parameters
Item | Parameter | |
Accessory power supply | AC 85~265V; DC100~300V; 50/60Hz | |
Power dissipation | < 8W | |
System voltage | AC 0~690V; DC 0~800V; 40~460Hz | |
System application | IT system (online), Other system (offline) | |
Insulation monitoring | Measuring range | 1k~10MΩ |
Alarm range | 10k~10MΩ | |
Resistance accuracy | 1~10k,1k; 10k~10M, ±10% | |
system leakage capacitance | <500μF | |
Response time (Ce=1μF) | <5s | |
Internal parameters | Measuring voltage | <50V |
Measuring current | <270μA | |
Internal DC impedance | ≥180kΩ | |
Relay output | Error, Alarm, Warning | |
SOE | 20 records (fault type, fault value, fault time) | |
Alarm type | LCD, LED indicator | |
Communication | RS485, Modbus-RTU | |
Impulse voltage / Pollution Leve | 8kV/III | |
EMC/ Radiation | IEC61326-2-4 | |
Environment | Working temperature | -10 ~+65ºC |
Storage temperature | -20~+70ºC | |
Relative humidity | <95%, without condensation | |
Altitude | ≤2500m |
LCD DisplayDimensionWiringTypical Connection
Our Contact